Cabin
88
Error code (FI)
Fig. 71:
Error in blow-out temperature sensor is indicated by flashing indicator (F1).
Note
The control unit has recorded an error in the blow-out temperature sensor.
The
control is no longer ready for operation.
Cause of sensor fault:
Short circuit or interruption in sensor line, plug connection on the sensor or control unit ,
temperature sensor defective. The controller will not be ready for operation again until the error
is eliminated. Then the sensor fault no longer appears.
Note
If a sensor fault occurs, the controller continues working with the setting that
was valid before the fault was recorded.